Page1
FLAG DROP TYPE FAULT INDICATOR
ZK TYPE
STRUCTURE
System: Flag Drop Type Fault Indicator
Indication & Reset operation: The fault signal generated by the outer protective relay contacts excites the operating coil and
drop the indication flag in the annunciator. The display window of the flag changes from the
normal condition of black to the fault condition of orange.
Pushing up the reset lever returns the indicator flag to the original position, and window
returns to normal condition black, if the fault signal was monentary and operating coil is not
excited any more.
Indication pattern: However, if the fault signal is continuous and still excites the operating coil, indicator flag in the
display window change to stripe pattern in orange and black by operating the reset lever. After
the fault signal is disappear the flag automatically return to the normal condition black.
●Operation
→ : Manual resetting
Normal condition Fault condition Continuous fault condition
(Black) (Orange) (Stripe pattern) → : Automatic resetting
SPECIFICATIONS (RATINGS, PERFORMANCE)
Specification Type Voltage operation type Current operation type
Rated insulation voltage (Ui) 250V
Voltage 24V, 48V, 100 / 110V, 125V, 200 / 220V AC / DC, 240V AC -
Coil rating
Current - 0.5A, 0.7A, 1.0A, 2.0A DC
Continuous input range 24V, 48V AC / DC: 80 to 130% Others: 70 to 130% 90 to 100% (in case of continuous input)
Operating value Rating X 70% max. Rating X 90% max.
Returning value Rating X 10% or more Rating X 10% or more
Minimum input pulse width
(rated voltage or current) 30 msec max. 30 msec max.
(200% input of rated current, 10 msec max.)
Operating time Flag interlock: 60ms or less Coil interlock: 30ms or less
External Terminal Faston #250 or screw terminal (M3.5)
Max. wire size 2mm2 max. (AWG14)
Insulation resistance 10MΩ or more (Between electric circuit block and ground) / 5MΩ or more (electric circuit between each other / Between contact terminals [Between poles])
Power frequency withstand voltage 2,000V AC (Between electric circuit block and ground / electric circuit between each other) / 1,000V AC (Between contact terminals [Between poles]) / 1 min.
Lightning impulse withstand voltage ±4.5kV (Between electric circuit block and ground / electric circuit between each other) / ±3kV (Between contact terminals [Between poles]) / 3 times for each poles (1.2 / 50µs)
Overload capability Rating X 1.3 times / 3 hours / 1 time Rating X 6.0 times / 30 sec. / 1 time
Contact current-carrying capacity 2A
Contact breaking capacity 110V DC, 0.2A (L/R = 7msec)
Vibration resistance Frequency: 16.7Hz, Width of frequency: 4mm, 10 min for each axis
Shock resistance 294m/s2, 3 times each axial direction
Durability 10,000 times or more (electrical, mechanical)
Protection degree Panel surface: IP40
Ambient operating temperature 0 to 40°C (–10 to 55°C: a few hours are allowed per day)
Storing temperature –20 to 60°C
Relative humidity 30 to 80% (average per day, no dew condensation)
Altitude 2,000 m max.
Weight Approx. 300g
* Please rafer to the page B70 for the technical data.
B61
Page2
PILOT LAMP & INDICATOR
FEATURES
The panel back size is shorter than The approximately 40% expansion of
TK type by about 25%. the name character area enhances
visibility of a nameplate.
24mm 28mm
133mm 100mm
TK Type ZK Type (Faston tab type)
110mm
TK Type ZK Type
A plug-in method for internal elements
is adopted, which enables easy
changing of specifications and
ZK Type (screw type) maintenance from the front of the
panel.
Faston / Tab type and Screw type
are available as standard line up.
Screw type is equiped with a
terminal cover.
Vertical and horizontal jumper for link
reduce wires.
Short time input operation is
available for current type.
(operating at 200% or more of rated current, * When removing the internal element, hang an
at input pulse of 10 msec). element unplugging tool on the lower hook to unplug
It sensitively responds to an pulse by lifting and removing the lock.
input signal to the annunciator relay.
For further details, refer to technical
information (page B70). Measures for whisker trouble are fully
prepared by eliminating the use of tin
and zinc plating.
4 contacts can be chosen from 2
contacts linked with the display flag
and 3 contacts linked with the coil
voltage.
Wide contact variations enable to Collective mounting is available, which
omit some auxiliary relays now in saves hole cutting work one by one.
use. It contributes to reduce man-hour.
(A vertical one-line assembly is not available).
B62
15mm
21mm
D ELECTRONIC DEVICES C CONNECTING DEVICES B PILOT LAMP & INDICATOR A SWITCH
Page3
FLAG DROP TYPE FAULT INDICATOR
ZK TYPE
HOW TO ORDER
■How to order as single unit
ZK - 120A - DC110V XX - O B F
① ② ③ ④ ⑤ ⑥ ⑦
■How to order internal elements
ZK-U - 120A - DC110V XX - O
① ② ③ ④ ⑤
No. Item Code Detail Note
ZK — —
① Basic type
ZK-U Internal element —
Flag interlock Coil interlock
000A — —
010A — 1a
020A — 2a
030A — 3a
020D — 1a1b
030E — 1a2b
(For further details, see Page B67 to B68.)
100A 1a —
② Contact arrangements 110A 1a 1a
Any contact arrangements other than
120A 1a 2a
those above are available.
130A 1a 3a
120D 1a 1a1b
120E 1a 2b
200A 2a —
210A 2a 1a
220A 2a 2a
300A 3a —
Coil rating Resistance value —
DC024V 24V DC 270Ω
DC048V 48V DC 1080Ω
DC110V 100 / 110V DC 4800Ω —
DC125V 125V DC 6900Ω
DC220V 200 / 220V DC 19500Ω
AC024V 24V AC 270Ω
③ AC048V 48V AC 1080Ω
Rated voltage / current
AC110V 100 / 110V AC 4800Ω Note: Voltage type AC rated product
AC125V 125V AC 6900Ω has a built-in 800V rated rectifier.
AC220V 200 / 220V AC 19500Ω
AC240V 240V AC 24100Ω
DC0.5A 0.5A DC 4.4Ω
DC0.7A 0.7A DC 2.1Ω
—
DC1.0A 1.0A DC 1.0Ω
DC2.0A 2.0A DC 0.28Ω
XX Standard specification —
④ Special specification
XZ Varistor mounted type Voltage type only
⑤ Flag color O Yellow-red (orange) When coil excitation continues after reset operation,
the flag color turns pattern black and orange.
⑥ Surface frame B Black (N1.5) —
S Screw terminal (M3.5) —
⑦ Rear surface terminal
F Faston tab #250 —
B63
Current operation type Voltage operation type
Page4
PILOT LAMP & INDICATOR
■How to order as assembled products
Collective mounting is available for ZK type. It is not necessary to make holes for each units,
and the assembled units can be installed in only one hole.
*We do not provide assembly services after the unit has been purchased.
*Items in a single vertical row cannot be produced.
1 In case of assembling the same specification
ZK - 02 x 03 - 120A - DC110VXX - OBF
Basic Vertical Horizontal Contact Rated voltage,
type number number arrangement Current
2 In case of assembling different specifications
Please enter the order sheet for ZK Drop Type Annunciator Relay attached to the page B63.
ZK - 02 x 03 - MIX - MIX - OBF
Basic Vertical Horizontal Contact Rated voltage,
type number number arrangement Current Order Sheet for ZK Type Fault Indicator
1 to 2 to 8
3 stages stages
Please refer to the above type coding for orders.
Please write “MIX” in “Contact arrangement” in
case of assembling different specifications of
contact arrangement.
Please write “MIX” in “Rated voltage, current”
in case of assembling different specifications
of rated voltage, current
About the layout drawing
Enclose the shape of the assembled window in
the layout drawing with a continuous line.
About the layout configuration
Fill the contact arrangement, rated voltage and
current, and rear terminal in the layout
configuration.
Precaution for assemblies
When ordering a collective type of rear terminal symbols S
(screw specification), please order after taking the wire size
and number of wires into account (there is a possibility that
wiring may be difficult depending on the wire size and
number of wires).
Table of sizes (mm)
Horizontal stage number
2 row 3 row 4 row 5 row 6 row 7 row 8 row
L1 72 108 144 180 216 252 288
L2 70
Sizes of collective mounting L3 81
Refer to the right table as to sizes of collective mounting L1 72 108 144 180 216 252 288
when mounting collectively. L2 140
A vertical one-line assembly is not available. L3 151
L1 72 108 144 180 216 252 288
L2 210
L3 221
B64
Vartical stage number
Third Second First
stage stage stage
D ELECTRONIC DEVICES C CONNECTING DEVICES B PILOT LAMP & INDICATOR A SWITCH
Page5
FLAG DROP TYPE FAULT INDICATOR
ZK TYPE
STANDARD PRODUCTS
ZK(Faston type) ●Outline
Mounting panel (t=1 to 6mm) Nameplate
holder
Display
window
Type NP Fitting tool
Tab terminal
#250 series Reset lever
Mounting hole size
〈When mounting a single unit〉
●Accessories
Internal element ZK-U- -
Nameplate ZK-DP(Sold separately)
Element unplugging tool TK-NQ(Sold separately)
Fitting tool ZK-TK(standard equipment)
ZK(Faston type [collective]) ●Outline
Fitting tool Mounting panel (t=1 to 6mm)
Rating . Contact arrangement NP
(In case different ratingscontact arrangements are mixed,
sealed under lower surfare)
Contact arrangement
Coil rating
Mounting hole size
●Accessories
Internal element ZK-U- -
Nameplate ZK-DP(Sold separately)
Element unplugging tool TK-NQ(Sold separately)
Fitting tool ZK-TK(standard equipment)
B65
Page6
PILOT LAMP & INDICATOR
ZK(Screw type) ●Outline
Mounting panel (t=1 to 6mm) Nameplate
holder
Display
window
Terminal cover
Type NP Fitting tool
Reset lever
Screw with
a square
washer
●Accessories
Mounting hole size
〈When mounting a single unit〉 Internal element ZK-U -
Nameplate ZK-DP(Sold separately)
Element unplugging tool TK-NQ(Sold separately)
Terminal cover ZK-CV(standard equipment)
Fitting tool ZK-TK(standard equipment)
Crimp terminal ZK-STSET(10 pcs attached)
Jumper ZK-SBV(Vertical linking()Sold separately)
*Caution Jumper ZK-SB36,50 (Horizontal linking()Sold separately)
When wiring assembled products, always verify the wire size, number of wires,
and other specifications.(As wiring may be difficult in some cases.)
ZK(Screw type [collective]) ●Outline
Fitting tool Mounting panel (t=1 to 6mm)
Terminal
cover
Rating . Contact arrangement NP
(In case different ratingscontact arrangements are mixed,
sealed under lower surfare)
Contact arrangement
Coil rating
Mounting hole size ●Accessories
Internal element ZK-U -
Nameplate ZK-DP(Sold separately)
Element unplugging tool TK-NQ(Sold separately)
Terminal cover ZK-CV(standard equipment)
Fitting tool ZK-TK(standard equipment)
Crimp terminal ZK-STSET(necessary pcs attached)
*Caution Jumper ZK-SBV(Vertical linking)(Sold separately)
When wiring assembled products, always verify the wire size, number of wires,
and other specifications.(As wiring may be difficult in some cases.) Jumper ZK-SB36(Horizontal linking)(Sold separately)
B66
D ELECTRONIC DEVICES C CONNECTING DEVICES B PILOT LAMP & INDICATOR A SWITCH
Page7
FLAG DROP TYPE FAULT INDICATOR
ZK TYPE
CONTACT ARRANGEMENTS AND SEQUENCES
About contact arrangement
Contact arrangement
symbol Operation chart
Terminal No.
ZK-120A Momentary fault Continuous fault
(+)9 7 5 3 1 9-10 Coil operation
1-2
3-4
Contact operation
30
, 5-6
a2 a2 a1 7-8
RESET Manual reset operation
(−)10 8 6 4 2
Indication
Contact Target indication
arrangement Black
circuit Stripe pattern
Orange
1 : Contact which interlocked with flag
2 : Contact which interlocked with coil
30 : Coil (Terminals # 9 and #10 fixed in all models)
ZK-000A Momentary fault Continuous fault ZK-030A Momentary fault Continuous fault
(+)9 7 5 3 1 9-10 (+)9 7 5 3 1 9-10
1-2 1-2
3-4 3-4
30 5-6 30
,, , 5-6
a2 a2 a2
7-8 7-8
RESET RESET
(−)10 8 6 4 2 (−)10 8 6 4 2
Indication Indication
ZK-010A Momentary fault Continuous fault ZK-020D Momentary fault Continuous fault
(+)9 7 5 3 1 9-10 (+)9 7 5 3 1 9-10
1-2 1-2
3-4 3-4
30 5-6 30 5-6
a2 b2 a2
7-8 7-8
RESET RESET
(−)10 8 6 4 2 (−)10 8 6 4 2
Indication Indication
ZK-020A Momentary fault Continuous fault Momentary fault Continuous fault
(+)9 7 5 3 1 9-10
1-2
3-4
30
, 5-6
a2 a2
7-8
RESET RESET
(−)10 8 6 4 2
Indication Indication
∗ Any contact arrangements other than those above are available. Please feel free to inquire.
B67
Page8
PILOT LAMP & INDICATOR
ZK-100A Momentary fault Continuous fault ZK-120E Momentary fault Continuous fault
(+)9 7 5 3 1 9-10 (+)9 7 5 3 1 9-10
1-2 1-2
3-4 3-4
30 5-6 30 5-6
a1 7-8 b2 b2 a1
7-8
RESET RESET
(−)10 8 6 4 2 (−)10 8 6 4 2
Indication Indication
ZK-110A Momentary fault Continuous fault ZK-200A Momentary fault Continuous fault
(+)9 7 5 3 1 9-10 (+)9 7 5 3 1 9-10
1-2 1-2
3-4 3-4
30 5-6 30
, 5-6
a2 a1 a1 a1
7-8 7-8
RESET RESET
(−)10 8 6 4 2 (−)10 8 6 4 2
Indication Indication
ZK-120A Momentary fault Continuous fault ZK-210A Momentary fault Continuous fault
(+)9 7 5 3 1 9-10 (+)9 7 5 3 1 9-10
1-2 1-2
3-4 3-4
30 30
, 5-6 , 5-6
a2 a2 a1 a2 a1 a1
7-8 7-8
RESET RESET
(−)10 8 6 4 2 (−)10 8 6 4 2
Indication Indication
Momentary fault Continuous fault ZK-220A Momentary fault Continuous fault
(+)9 7 5 3 1 9-10
1-2
3-4
30
, , 5-6
a2 a2 a1 a1 7-8
RESET RESET
(−)10 8 6 4 2
Indication Indication
ZK-120D Momentary fault Continuous fault Momentary fault Continuous fault
(+)9 7 5 3 1 9-10
1-2
3-4
30 5-6
b2 a2 a1
7-8
RESET RESET
(−)10 8 6 4 2
Indication Indication
∗ Any contact arrangements other than those above are available. Please feel free to inquire.
B68
D ELECTRONIC DEVICES C CONNECTING DEVICES B PILOT LAMP & INDICATOR A SWITCH
Page9
FLAG DROP TYPE FAULT INDICATOR
ZK TYPE
ACCESSORIES
Element extraction tool Fitting tool (Order unit: 10)
● (Order unit: 10)
TK-NQ ●ZK-TK
Standard equipment
Jumper (Order unit: 100)
For rear terminal symbol S (screw specification)
ZK-SBV ZK-SB36 ZK-SB50
Vertical linking Horizontal linking (36mm pitch) Horizontal linking (50mm pitch)
For vertical adjacent terminals For upper stage terminals of min. pitch For upper stage terminals of
instration (36mm) or assembled type 50mm pitch instration
Terminal cover (Order unit: 100) Nameplate (Order unit: 100)
For rear terminal symbol S (screw specification) (Acryl material t = 1mm)
●ZK-CV ●ZK-DP
Commercial cardboards
are also available
21mm instead of ZK-DP.
67mm
Standard equipment
30.5mm
27.5mm
Cramp terminal (Order unit: 10)
●ZK-ST SET
(10 pcs)
Standard accessory for screw type.
B69
Page10
PILOT LAMP & INDICATOR
TECHNICAL DATA
Operating condition of current type
For the current operation type, it is sometimes used by connecting in series with a relay equipped
with a self-cutoff contact in the manner shown in Figure 1; in that case, current I shows the waveform
shown in Figure 2 depending on the coil inductance of those serial relays.
Voltage V waveform
P
Relay
Ry
Current waveform Calculated
circuit current
value
Voltage
V Calculated
circuit current
value
Current ZK
30
200% or more
current of rating Rectangle
N 1
10 msec or more
Figure 2. Voltage and current waveform
When high-speed operation is required (operation at 200% or more of rated current and minimum input pulse of 10
msec or less), please select a coil rating that can secure a rectangle 1 within the actual circuit current waveform.
High-speed operation is confirmed in the condition with the resistance value of the serial relay (Fig. 1 Ry) in the
following table.
Coil rating of F ault Indicator Relay resis tance value
0.5A DC 36.7Ω
0.7A DC 26.2Ω
1A DC 18.3Ω
2A DC 9.2Ω
Ratings, performance
No. Specification Ratings, performance
1 Contact circuit resistance 150mΩ or less (voltage drop method 1A current flow measurement)
2 Contact circuit current 2A
Resistive 110V DC 2A
load 220V AC 2A
3 Contact rated load 110V DC 0.2A (L/R = 7ms)
Inductive 24V DC 1.5A (L/R = 7ms)
load 220V AC 0.8A (cosφ = 0.4)
24V AC 2.0A (cosφ = 0.4)
Contact circuit resistance is the resistance between the outside box terminals of a contact circuit.
B70